Disjoncteur moteur SCHNEIDER – 1-1.6A – 3 Pôles – déclencheur magnéto-thermique

Description :

Caractéristiques techniques principales :

range TeSys
TeSys Deca
product name TeSys GV2
TeSys Deca
product or component type Circuit breaker
device short name GV2ME
device application Motor
trip unit technology Thermal-magnetic

 

Informations complémentaires :

poles description 3P
network type AC
utilisation category AC-3 conforming to IEC 60947-4-1
Category A conforming to IEC 60947-2
network frequency 50/60 Hz conforming to IEC 60947-4-1
fixing mode 35 mm symmetrical DIN rail: clipped
Panel: screwed (with adaptor plate)
operating position Any position
motor power kW 0.37 kW at 400/415 V AC 50/60 Hz
0.37 kW at 500 V AC 50/60 Hz
0.75 kW at 690 V AC 50/60 Hz
0.55 kW at 400/415 V AC 50/60 Hz
0.55 kW at 500 V AC 50/60 Hz
0.75 kW at 500 V AC 50/60 Hz
1.1 kW at 690 V AC 50/60 Hz
breaking capacity 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
control type Push-button
[In] rated current 1.6 A
thermal protection adjustment range 1…1.6 A
magnetic tripping current 22.5 A
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ith] conventional free air thermal current 1.6 A conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2
power dissipation per pole 2.5 W
mechanical durability 100000 cycles
electrical durability 100000 cycles for AC-3 at 440 V
maximum operating rate 25 cyc/h
rated duty Continuous conforming to IEC 60947-4-1
tightening torque 1.7 N.m on screw clamp terminals
suitability for isolation Yes conforming to IEC 60947-1
phase failure sensitivity Yes conforming to IEC 60947-4-1
height 89 mm
width 45 mm
depth 78.5 mm
net weight 0.26 kg
colour Dark grey