Sélectionner une page

Contacteur SCHNEIDER 4P (2F+2O) AC-1 – 440V – 20A – Bobine 48Vcc

UGS : LP1K09008ED Catégorie :
UGS : LP1K09008ED Catégorie :

Description :

Caractéristiques techniques :

range of product TeSys K
range TeSys
product or component type Contactor
device short name LP1K
contactor application Resistive load
utilisation category AC-1
poles description 4P
pole contact composition 2 NO + 2 NC
[Ie] rated operational current 20 A (at <50 °C) at <= 440 V AC AC-1 for power circuit
16 A (at <70 °C) at 690 V AC AC-1 for power circuit

 

Informations complémentaires :

control circuit voltage limits Operational: 0.8…1.15 Uc (at <50 °C)
Drop-out: 0.1…0.75 Uc (at <50 °C)
[Ui] rated insulation voltage Power circuit: 600 V conforming to UL 508
Power circuit: 690 V conforming to IEC 60947-4-1
Power circuit: 600 V conforming to CSA C22.2 No 14
[Uimp] rated impulse withstand voltage 8 kV
overvoltage category III
mounting support Plate
Rail
flame retardance V1 conforming to UL 94
Requirement 2 conforming to NF F 16-101
Requirement 2 conforming to NF F 16-102
tightening torque 1.3 N.m – on screw clamp terminals – with screwdriver Philips No 2
1.3 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm
[Ue] rated operational voltage Power circuit: 690 V AC 50/60 Hz
[Ith] conventional free air thermal current 20 A (at 50 °C) for power circuit
Irms rated making capacity 110 A AC for power circuit conforming to NF C 63-110
110 A AC for power circuit conforming to IEC 60947
rated breaking capacity 110 A at 415 V conforming to IEC 60947
110 A at 440 V conforming to IEC 60947
80 A at 500 V conforming to IEC 60947
110 A at 220…230 V conforming to IEC 60947
110 A at 380…400 V conforming to IEC 60947
70 A at 660…690 V conforming to IEC 60947
associated fuse rating 25 A gG at <= 440 V for power circuit
25 A aM for power circuit
average impedance 3 mOhm – Ith 20 A 50 Hz for power circuit
inrush power in W 3 W (at 20 °C)
hold-in power consumption in W 3 W at 20 °C
operating time 30…40 ms coil energisation and NO closing
10 ms coil de-energisation and NO opening
25…35 ms coil energisation and NC opening
15 ms coil de-energisation and NC closing
safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
mechanical durability 10 Mcycles
maximum operating rate 3600 cyc/h
height 58 mm
width 45 mm
depth 57 mm
net weight 0.225 kg